Top 5 Ways to Trash Your Pump

One critical component in your pump is the coupling that might be connecting your motor to the pump.  In the case of fire pump for example, it would be a grid coupling.  Like other coupling types, grid couplings often have "signature failures" modes that can completely make your pump fail.
In the case of fire pumps, where a flex or grid coupling is recommended (as per NFPA standards), here are 5 reasons that may cause grid coupling failures:

1) Reversing or highly fluctuating loads
Figure 1 - Fatigue Wear
Fatigue failures are typically due to high start-up or impact loads and/or in combination with reversing or highly fluctuating loadsSignature fatigue wear, which can generally be viewed as normal grid coupling wear, shows up as cracks in the grid spring element approximately in the center of the grid spring element legs (see Figure 1 – Fatigue Wear).

With a few grid spring element legs broken in the center, a grid coupling will likely still be operational and transmitting torque through the remaining unbroken legs. However, once such a condition occurs, the coupling is operating in a compromised state and the grid spring element should be replaced as soon as possible.
2) Undersized Coupling 
A bad combination of undersized coupling and peak torque load(s) in excess of the calculated coupling sizing torque can cause a torque overload.  In this situation, the cracks in the grid spring element legs are not centered but rather further up or down the center 
3) Lack of Lubrication
Not lubricating the coupling properly can lead to failures.   In this case, the cracks are often localized to one side of a grid spring (where lubrication was lacking) and may resemble or look like a fatigue failure. The grid coupling is a metal-on-metal coupling, and a lack of lubrication will lead to premature wear (or fatigue) of the grid spring element. (How should you pack the grease in a Grid Coupling?).

4) Misalignment
Figure 2 - Misalignment Failure
A grid coupling is an excellent vibration dampening high power density coupling.  They are unfortunately not very good at accommodating misalignment. Grid couplings are not designed to handle parallel shaft misalignment, they are only designed to handle about a quarter degree of angular misalignment (see How sensitive are Grid Couplings to misalignment?).

Figure 2 is an example of a grid coupling element misalignment failure.  In such a failure, the grid spring break on the outer bends of the grid spring legs. Similar to fatigue failures, a grid coupling may have broken legs due to misalignment and still transmitting torque through the unbroken legs. This is not a desirable long term state and the grid spring should be replaced as soon as possible.  To prevent such failures (or to correct from such a failure from re-occurring), it is critical that the coupling shafts be realigned and within the misalignment tolerance of the given grid coupling. 

5) Excessive temperature and/or chemical exposure
Environmental conditions include excessive temperature and/or chemical exposure. Operational temperatures above or below the temperature range of the grid coupling seals will lead to seal damage or failure. Similarly, grease can also break down given extreme temperature exposure. Chemicals can also lead to seal damage and failure. In addition to visible damage to seals and lubrication breakdown, environmental failures may appear similar to an overload condition.  

To learn more about Grid Couplings, please read Why a Grid Coupling - Features & Benefits, Design Basics, and Element Options

Friday, December 19, 2014

Grid Coupling Failure Analysis (includes photos)

Like other coupling types, grid couplings often have "signature failures" modes that can help root cause a given coupling's failure. Some of the common causes of grid coupling failures are fatigue, torque overload, lack of lubrication, misalignment, and environmental conditions.


Grid Coupling - Fatigue WearFatigue Wear


Signature fatigue wear, which can generally be viewed as normal grid coupling wear, shows up as cracks in the grid spring element approximately in the center of the grid spring element legs (as pictured at right).

With a few grid spring element legs broken in the center, a grid coupling will likely still be operational and transmitting torque through the remaining unbroken legs. However, once such a condition occurs, the coupling is operating in compromised state and the grid spring element should be replaced as soon as possible. 


Torque Overload 


Torque overload failures appear similar to fatigue wear, but the cracked grid spring element legs are not centered but rather further up or down on the given grid spring element legs.


Lack of Lubrication


Failures due to a lack of lubrication are often localized to one side of a grid spring (where lubrication was lacking) and may resemble or look like a fatigue failure. The reason for this is a grid coupling is a metal-on-metal coupling, and a lack of lubrication will lead to premature wear (or fatigue) of the grid spring element wherever there is not adequate lubrication (see How should you pack the grease in a Grid Coupling?).


Grid Coupling - Misalignment WearMisalignment


While grid couplings are a very good vibration dampening high power density coupling, they are unfortunately not very good at accommodating misalignment. They are not designed to handle any parallel shaft misalignment, and are only designed to handle about a quarter degree of angular misalignment (see How sensitive are Grid Couplings to misalignment?).

Pictured at right is an example of a grid coupling element misalignment failure.  In such a failure, the grid spring break on the outer bends of the grid spring legs. Similar to fatigue failures, a grid coupling may have broken legs due to misalignment and still transmitting torque through the unbroken legs. This is not a desirable long term state. The grid spring should be replaced as soon as possible, and to prevent such failures (or to correct from such a failure from re-occurring) it is critical that the coupling shafts be realigned and within the misalignment tolerance of the given grid coupling.

 

Environmental Conditions


Environmental conditions include excessive temperature and/or chemical exposure. Operational temperatures above or below the temperature range of the grid coupling seals will lead to seal damage or failure. Similarly, grease can also break down given extreme temperature exposure. Chemicals can also lead to seal damage and failure. In addition to visible damage to seals and lubrication breakdown, environmental failures may appear similar to an overload condition. 

To learn more about Grid Couplings, please read Why a Grid Coupling - Features & Benefits, Design Basics, and Element Options

To learn more about coupling failure analysis, visit:
Coupling Failure Analysis - Jaw Couplings (includes hub & spider photos)
Gear Coupling Tutorial - Part V: Failure Analysis (with photos)
Coupling Peak Torque Failure at Keyway
Top Reason for a Coupling Failure